Check Delivery Status Here


|
|
|
|
|
Images
are for
illustrative purposes only
|
|
|
|
|
1100VC | Apollo 1000VA Line Interactive UPS W/7AH BATTERY*2
SKU
1100VC
Apollo 1000VA Line Interactive UPS W/7AH BATTERY*2 Retail Box 1 year Warranty Power Levels created at nominal inputs 1000VA/550W Output Voltage 200V/220V/230V/240V Selectable Voltage Waveform Step wave Output Frequency 50/60Hz Over current protection Voltage 12V/7Ah x2pcs Smart pulse charging with two charging modes. Interface port USB,RJ45 (Surge Protection) Control panel LCD or LED Selectable Accessories:Software included (2 backup ;2 surge)+built-in AVR,overload/shortage protection, LCD display Line Interactive
|
Battery
|
| |
Backup Time
|
Full load 850VA/1500VA: 3.5 minutes Half Load 850VA/1500VA: 12 minutes
|
| |
Battery type
|
Maintenance –free sealed, valve-regulate1000VA/1500VA, 2pcsd, Lead-Acid, 12V, 7Ah
|
| |
Voltage
|
12V/7Ah x2pcs
|
| |
Charging method
|
Smart pulse charging with two charging modes. Quick charging when battery is not fully charged, trickle charging when battery is 90% fully charged.
|
| |
Charging time
|
5~8hrs
|
| |
Average charging current
|
650VA/850VA: 0.6A 1000VA/1500VA: 1A
|
| |
Average charging voltage for each Batt.
|
Quick charging mode: 14V maximum. Trickle charging mode: 13.2V ~13.9V adjustable by using the setting software
|
| |
Protection
|
Over charging voltage protection. (CPU control + Circuit control) Thermo protection. (CPU control) When temperature inside UPS is over 45℃ charger will stop charging for 2.5 minutes followed by an 1.5 minutes charging, the cycle will repeat until the temperate is lower than 44℃.
|
| |
Monitoring
|
Smart monitoring for failed battery or battery open circuit detection and warning, Auto-detect every time when power on and auto repeat the detection every 6 days
|
| |
|
Communications & Management
|
| |
Interface port
|
USB, RJ45 (Surge Protection)
|
| |
Control panel
|
LCD or LED Selectable
|
| |
Audible alarm
|
On battery alarm: Low battery alarm, Battery over voltage alarm Over load alarm: Short-circuit alarm, Thermal alarm
|
| |
Green mode function (Auto-shutdown during blackout)
|
1% to 14% of full load (adjustable with the setting software) The default setting is OFF.
|
| |
|
Output
|
| |
Voltage
|
100V/110V/115V/120V Selectable or 200V/220V/230V/240V Selectable
|
| |
Frequency
|
50/60Hz
|
| |
Regulation
|
(Nominal) ±10% (AVR) (Battery mode) ±5% of selected output voltage
|
| |
Waveform
|
Step wave
|
| |
Power Level
|
1000VA/550W
|
| |
Crest Factor
|
2:1
|
| |
Transfer time
|
Blackout 5ms typical Brownout 3ms typical Battery mode to Normal mode:3ms typical
|
| |
Over current protection
|
Over load alarm level 100% ~ 120%, Over load shutdown level 120% ~ 190% (Adjustable with the remote set-up software)
|
| |
|
Power Specifications
|
| |
Voltage Range
|
-33% ~ +28%
|
| |
Frequency
|
47Hz ~ 65Hz, 50/60Hz auto-sensing
|
| |
Nominal Voltage
|
100V/110V/115V/120V Selectable or 200V/220V/230V/240V Selectable
|
| |
Over current protection
|
By reset-able over current protector
|
| |
AVR Range (One Buck, Two Boosts)
|
Buck mode: +9% for selected nominal voltage. Boost mode: -9% for selected nominal voltage. Enhanced Boost: -22% for selected nominal voltage.
|
| |
Surge Protection
|
220 Joules
|